All transformers undergo standard commercial tests, including:
No-Load Losses: Tested at rated current.
Load Losses: Total losses at rated current.
Percent Impedance: Measured at rated current.
Excitation Current Test: Conducted at 100% voltage.
Ratio Tests: Performed across all tap settings.
Polarity and Phase Relation Tests: Ensures proper orientation.
Induced Potential Tests: Verifies durability under operational conditions.
Impulse Tests: Full wave and reduced wave performance analysis.
Specification | Details |
---|---|
KVA Ratings | 25, 50, 75, 100, 125, and 150 |
No. of Phases | Single-Phase |
Frequency | 60 Hz |
Primary Voltage | 2,400 V – 19,920 V |
Secondary Voltage | 120 V – 600 V |
Tapping Range | ±2 × 2.5% |
Winding Material | Copper, Aluminum |
Cooling Type | ONAN, KNAN |
Feed Type | Loop Feed, Radial Feed |
Fluid Type | Non-PCB Mineral Oil |
Connection Type | Dead Front |
Mounting | Pad-Mounted |
Sound Level: Compliant with NEMA TR1 Standard.
IEEE Compliance: Meets IEEE C57.12.00 Standards.
UL Certification: UL Listed.
Efficiency: DOE 2016 Standard Compliant.
Temperature Rise Options: 65°C, 65/75°C, 75°C.
Enclosure Type: NEMA Type 3R – Stainless Steel.
Bay-O-Net Expulsion Fuse: Standard protection feature.
MOV Surge Arrestor: Available on demand.
Tank Material: Coated Steel.
Tank Coating System: Complies with IEEE Std C57.12.28 and C57.12.29.
Quality System: ISO 9001 Certified.
Routine Tests: Conducted in accordance with ANSI® and IEEE®.
Warranty: Industry-standard coverage provided.