PRODUCT OVERVIEW

Substation Transformer

Powering Safe & Efficient Energy Distribution

Transformer Dimensions and Ratings

KVA Ratings
500, 1000, 1500, 2000, 2500, 5000 and higher
No. of Phases
Three-Phase
Frequency
50 Hz – 60 Hz
Primary Voltage
Up to 230 kV
Secondary Voltage
120 V – 69 kV
Tapping Range
±5% or ±10%
Winding Material
Copper, Aluminum
Cooling Type
ONAN, ONAF
Fluid Type
Non-PCB Mineral Oil or FR3 Fluid
Connection Type
Delta-Wye
Mounting
Stationary Substation Installation
Transformer Testing (ANSI C57.12.90)
All substation transformers undergo the following standard commercial tests:
No-Load Losses
Evaluated at rated voltage
Load Losses
Measured under rated conditions
Percent Impedance
Calculated at rated current
Excitation Current Test
Conducted at 100% voltage
Ratio Tests
Ensured across all tap settings
Polarity and Phase Relation Tests
Verifies orientation
Induced Potential Tests
Simulates electrical stress scenarios
Impulse Tests
Full wave and reduced wave performance tested
Standards and Certifications
Sound Level
Designed to meet NEMA Noise Standards
IEEE Compliance
Conforms to IEEE C57.12.10 Standards
UL Certification
UL Listed and Compliant
Efficiency
Meets DOE 2016 Efficiency Standards or higher
Temperature Rise Options
55°C, 65°C, 65/75°C
Primary Protection Devices
Internal Fuses
Current-limiting types for overcurrent protection
External Surge Arresters
Available for high-voltage applications
Tank and Material Specifications
Tank Material
Mild Steel or Stainless Steel with advanced coating systems
Tank Coating System
Complies with IEEE Std C57.12.28 for durability
Enclosure Type
Weather-resistant construction suitable for outdoor substation environments
Quality Control and Warranty
Quality System
ISO 9001 Certified
Routine Tests
Conducted per ANSI® and IEEE® standards
Warranty
Industry-standard coverage for defects and performance

Power Transformers

Rated Capacity (kVA) High Voltage (kV) Tapping Range Low Voltage (kV) Vector Group No-load Loss (%) Impedance Voltage (%) No-load Losses (kW) On-load Losses (kW)
6300
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.77
630
9.3
36
8000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.77
910
11.2
45
10000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.72
1310
13.2
53
12500
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.72
1580
15.6
63
16000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.67
1890
18.8
77
20000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.67
2310
22.0
93
25000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.62
2730
26.0
110
31500
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.60
3200
30.8
133
40000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.56
3830
36.8
156
50000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.52
4540
44.0
194
63000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.48
5410
52.0
234
75000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.42
6200
59.0
278
90000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.38
7500
68.0
320
120000
110,
112
±2×2.5%
6.3, 6.6,
10.5, 11
YNd11
0.34
10300
84.8
397
Rated Capacity (kVA) High Voltage (kV) Tapping Range Low Voltage (kV) Vector Group No-load Current (%) Impedance Voltage (%) - Step Up Impedance Voltage (%) - Step Down No-load Losses (kW) On-load Losses (kW)
6300
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.82
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
11.2
47.0
8000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.78
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
13.2
56.0
10000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.74
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
15.8
66.0
12500
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.70
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
18.4
78.0
16000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.68
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
22.4
94.0
20000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.65
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
26.4
112.0
25000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.60
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
30.8
133.0
31500
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.58
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
36.8
157.0
40000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.56
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
43.6
189.0
50000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.55
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
52.0
225.0
63000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.55
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
61.6
270.0
75000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.50
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
70.2
307.7
80000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.50
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
73.7
323.0
120000
110±2×2.5%,
121±2×2.5%
35,
38.5
6.3, 6.6 / 10.5, 11
Yyn0d11
0.50
HV–MV: 17.5–18.5HV–LV: 17.5–18.5MV–LV: 6.5
HV–MV: 10.5HV–LV: 17.5–18.5MV–LV: 6.5
87.1
381.8

Power & Auto Transformers (69–765 kV | up to 1500 MVA)

Category Recommended Technical Fields
Electrical Ratings
HV/MV/LV ratings, phases (1Φ/3Φ), vector group (YNd11, Yy0, etc.), frequency (50/60 Hz)
Thermal Performance
Cooling method (ONAN, ONAF, OFAF), winding temperature rise (65/75 °C), hot-spot limit
Tap-Changer
OLTC/NLTC type, voltage range (±2×2.5%, ±4×1.25%), number of steps, rated current
Losses & Efficiency
No-load losses (kW), load losses (kW), guaranteed efficiency at 25%, 50%, 100% load
Impedance
%Z @ rated MVA, short-circuit withstand level, positive/zero sequence impedance
Insulation & BIL
Lightning impulse (LI), switching impulse (SI), power frequency withstand levels (kV)
Sound & Vibration
Guaranteed sound level (dBA), vibration isolators
Mechanical Data
Core material, core configuration (3-limb/5-limb), total weight, transport weight, tank size
Testing & Compliance
IEC 60076, ANSI C57, routine/type/special test checklist
Accessories
Bushing type (OIP/RIP), PRD, Buchholz relay, oil level indicators, digital temp monitors

HVDC Converter Transformers (±50 kV to ±800 kV)

Category Recommended Technical Fields
Electrical Ratings
Valve/line side voltages, MVA rating, bipolar/monopolar configuration
DC Specific Design
DC bias withstand, harmonic withstand (% THD), dielectric clearances for DC and impulse
Tap-Changer
OLTC with extended range (up to ±25%), adaptive voltage control
Impedance
% impedance (e.g., 15–18%), leakage reactance
Losses & Heating
Losses under harmonic-rich conditions, hotspot rise under composite loads
Cooling System
OFAF or ODAF with oil flow management system
Testing
Dual-frequency tests, polarity reversal, lightning impulse, switching impulse, chopped wave
Accessories
Valve bushings, smoothing reactor terminals, shielding devices, external tap boxes

Rectifier & Arc Furnace Transformers (35–220 kV | up to 140 MVA)

Category Recommended Technical Fields
Electrical Ratings
HV/rectifier side voltage, MVA rating, phase configuration, connection group
DC Output Spec
Secondary voltage, max DC current (e.g., 44,000 A), number of pulse (6/12-pulse)
Short Circuit Design
Dynamic forces, bracing, %Z (typ. 7–9%), short-circuit duration withstand
Cooling
ONAN/ODAF with overload profile, forced oil flow control
Losses & Overload
Total losses, overload curves (15 min, 30 min), transient thermal limits
Tap-Changer
Off-load or on-load tapper, especially for arc voltage regulation
Testing
Impulse withstand, thermal cycle, core hot spot monitoring
Accessories
Current transformers, temperature alarms, explosion vent

Shunt Reactors (35–1000 kV | up to 320 MVAr)

Category Recommended Technical Fields
Voltage Ratings
Nominal voltage, phase (1Φ/3Φ), insulation class
MVAr Capacity
Rated reactive power, core/reactor type (gapped core, air-core, iron-core)
Impedance & Inductance
Nominal inductance, total loss (core + stray), Q factor
Losses
No-load loss < 0.5%, stray losses, load factor impact
Cooling
Natural air (dry), ONAN, ONAF
Noise Level
≤ 65–75 dBA
Impulse Ratings
LIWL, PF withstands
Mounting
Skid type or platform-based
Testing
Magnetic balance, induced voltage, high voltage withstand

Cast Coil Dry-Type Transformers (10–35 kV | up to 20 MVA)

Category Recommended Technical Fields
Electrical Ratings
Rated voltage, class, number of windings, insulation class
Insulation System
Vacuum cast epoxy resin, class F/H, PD-free at 1.1 x rated voltage
Cooling
AN, AF; natural/forced air cooling, with vented enclosure
Losses
Core loss, load loss, thermal rise (max 100 °C)
Impedance
4–8% depending on kVA class
Protection Class
IP00, IP23, or up to IP44 for special installations
Testing
Induced voltage, heat run, lightning impulse, PD measurement
Accessories
Temperature sensors, protection relays, enclosure panels

Railway Traction Transformers (≤35 kV | ≤20 MVA)

Category Recommended Technical Fields
Electrical Ratings
Input/output voltage, Vv/Scott-T wiring scheme, KVA rating
Tap-Changer
Off-load or on-load ±2×2.5%, automatic tap position logic
Load Balancing
Phase load equalization curve, impedance per leg
Thermal & Overload
Thermal withstand under cyclic loading, ambient temperature profile
Short Circuit Strength
Fault withstand, electromagnetic design, bracing details
Protection & Monitoring
Bushing sensors, Buchholz relay, pressure relief, oil temp gauge
Testing
Railway-specific: vibration endurance, high surge withstand, harmonics